FKS-KWS Chiller for Liquids
Benefits
- Compact design
- ATEX/CSA certified
- Ambient temperature range of -20 °C to +55 °C (-4 °F to +131 °F)
- Various refrigerating capacities
Marking
Marking ATEX:
Ex II 2G IIC T3 or T4 Gb (chiller)
EX II 2G Ex d e [ia] IIC T4 Gb (control unit)
Certification: TÜV 06 ATEX 2958
Marking
NEC 500: Class I, Div. 2, Group B, C or D, T3 or T4
NEC 505: Class I, Zone 1,
Chiller: AEx px mb de IIB+H2 T3 or T4
Control Unit: AEx px de [ia] IIB+H2 T4
CEC section 18:
Chiller: Ex px mb de IIB+H2 T3 or T4
Control Unit: Ex de [ia] IIB+H2 T4
Certification: CSA 2066361
Ambient Temperature
T3 or T4Description
The closed loop chillers consist of an air-cooled high performance condenser combined with an encapsulated compressor. They are suitable for the installation in explosive gas atmospheres defined as Zone 1. The electrical control system is supplied with its own Ex d housing. Optionally, with an analyzer, the control system can be placed inside the Ex p housing of the analyzer. Problems on-site where utilities supplied cooling water is of a lower quality or special requirements of cooling water are needed, closed loop chillers can be applied to meet these applications. The chillers can be supplied with diverse refrigerating capacities which allow the chillers to be used on single analyzers up to complete analyzer houses, peltier elements and heat exchangers. They can be delivered suitable for indoor or outdoor use. Depending on the flow rate required, different pump capacities are also available.
Technical Data
Refrigerating capacity at coolant temperature, water outlet | FKS 0.5-KWS typical 500 W at -35 °C (-31 °F) FKS 1.4-KWS typical 1.4 kW at +15 °C (+59 °F) FKS 2.4-KWS typical 2.4 kW at +10 °C (+50 °F) FKS 4-KWS typical 4 kW at +10 °C (+50 °F) FKS 6-KWS typical 6 kW at +10 °C (+50 °F) FKS 10-KWS typical 10 kW at +10 °C (+50 °F) |
---|---|
Refrigerant | R134a (R449a FKS 0.5-KWS) |
Coolant | temper/water/glycol (depending on application) |
Coolant temperature range | FKS 0.5-KWS -35 °C to +10 °C (-31 °F to +50 °F) FKS 1.4-KWS to FKS 10-KWS -5 °C to +28 °C (+23 °F to +82 °F) |
Circulation pump capacity ±10 % | FKS 0.5-KWS 400 l/h, 2 to 3 bar FKS 1.4-KWS 360 l/h, 2 to 4 bar FKS 2.4-KWS 450 l/h, 2 to 4 bar FKS 4-KWS 600 l/h, 2 to 4 bar FKS 6-KWS 1000 l/h, 2 to 3 bar FKS 10-KWS 1500 l/h, 2 to 3 bar |
Power consumption (effective power) | FKS 0.5-KWS 3.7 kW FKS 1.4-KWS 1.8 kW FKS 2.4-KWS 2.3 kW FKS 4-KWS 3.2 kW FKS 6-KWS 4.3 kW FKS 10-KWS 6.5 kW |
Ambient conditions | standard: +5 °C to +40 °C (+41 °F to +104 °F) Option: -20 °C to +55 °C (-4 °F to +131 °F) FKS 0.5-KWS +5 °C to +35 °C other ranges on request IP 54 (IP 65 on request) (comparable NEMA 12, NEMA 3 on request |
General alarm/fault indication | potential-free contact (1 NC + 1 NO) |
Tube fittings | FKS 0.5-KWS to FKS 2.4-KWS, ½ inch NPT FKS 4-KWS to FKS 10-KWS, depending on application |
Weight, dimensions (HxW D) | FKS 0.5-KWS: 600 x 960 x 530 mm 150 kg FKS 1.4-KWS: 500 x 960 x 530 mm 150 kg FKS 2.4-KWS: 600 x 960 x 530 mm 160 kg FKS 4-KWS: 1000 x 1100 x 700 mm 260 kg FKS 6-KWS: 1100 x 1100 x 700 mm 290 kg FKS 10-KWS: 1200 x 1100 x 700 mm 310 kg |
Data Sheets
-
FKS-KWS_Chiller for Liquids_datasheet.pdf
Brochures
-
FKS-KWS_Chiller for Liquids_brochure.pdf