APEXpy
Benefits
- Black box system
- Automatic calculation of the purge time
- WEB interface
- 3 x PT100/1000 inputs
- Modular design
- Safety-related control system
- Separate purge gas input and output
Marking
ATEX:
Ex II 2(1)G
Ex eb mb ib [ib pyb] [ia Ga] IIC T4 Gb
Ex eb mb ib [ib pyb] [ia Ga] IIC T5 Gb
Ex III 2(1)D
Ex tb [ib pyb] [ia Da] IIIC T130 °C Db
Ex tb [ib pyb] [ia Da] IIIC T95 °C Db
IECEx:
Ex eb mb ib [ib pyb] [ia Ga] IIC T4 Gb
Ex eb mb ib [ib pyb] [ia Ga] IIC T5 Gb
Ex tb [ib pyb] [ia Da] IIIC T130 °C Db
Ex tb [ib pyb] [ia Da] IIIC T95 °C Db
Ambient Temperature
Operating temperature-25 °C to +60 °C @ T4
(-13 °F to 140 °F @ T4)
-25 °C to +50 °C @ T5
(-13 °F to 122 °F @ T5)
Storage temperature
-20 °C to +60 °C
(-4 °F to 140 °F)
Product Video
Description
The APEXpy Ex p control unit controls and monitors the pre-purge and operating phase of pressurised enclosure equipment protected in accordance with ignition protection type pyb. Digital or proportional purge gas valves can be used.
The parameters can be set using the integrated WEB interface or the optionally available p operator panel. The APEXpy features two release relays; one which is energised and one which has floating contacts. Two signal relays with one changeover contact each are additionally available.
Three PT100/1000 inputs are available to monitor the temperature of the Ex p-protected equipment. Up to three switch values can be assigned to them.
Model II comes complete with integrated pressure measurement.
The following components are additionally required to set up a complete control system:
- Pressure monitor
- Purge gas valve, proportional or digital
- Valve fuse
- Pressure reducer
- There is the option to connect a p operator panel
Technical Data
Protection class | IP 66 according to EN/IEC 60529 IP 64 according to EN/IEC 60079-0 |
---|---|
Pressure range | 0 to 25 mbar for all pressure switching levels |
Purge time | 0 to 120 minutes (adjustable) |
Temperatures | Operating temperature -25 °C to +60 °C @ T4 (-13 °F to 140 °F @ T4) -25 °C to +50 °C @ T5 (-13 °F to 104 °F @ T5) Storage temperature -20 °C to +60 °C (-4 °F to 140 °F) |
Voltage | AC Variant: AC 100 V up to 230 V DC Variant: DC 24 V up to 44 V |
Material | V4A stainless steel |
Display | 6 LEDs for status display |
Relay | Enable contact, switched input voltage max. load 5A Enable relay, potentiel free, 4 NO 2x Signal relay for status transmission (potentail free), CO |
Weight | 6.8 kg |