Product SILASmv

SILASmv

Ex p control unit for zone 2/22 - separate variant
A7-37S2-2111-510

Benefits

  • Black box system
  • Automatic calculation of the purge time
  • WEB interface
  • 3 x PT100/1000 inputs
Get a Quote

Marking

ATEX:
Ex II 3G Ex ec mc ic [ic pzc] IIC T4 Gb
Ex II 3D Ex tc [ic pzc] IIIC T130 °C Db

IECEx:
Ex ec mc ic [ic pzc] IIC T4 Gb
Ex tc [ic pzc] IIIC T130 °C Db

Ambient Temperature

Operating temperature
-25 °C to +50 °C @ T4
(-13 °F to 140 °F @ T4)

Storage temperature
-20 °C to +60 °C
(-4 °F to 140 °F)

Certification

Description

The SILASmv Ex p control unit controls and monitors the purge and operating phase of small, separate, pressurised enclosure equipment protected in accordance with ignition protection type pzc.

The parameters can be set using the integrated WEB interface or the optionally available p operator panel.

The SILASmv features two release relays; one which is energised and one which has floating contacts. Two signal relays with one changeover contact each are additionally available. Three PT100/1000 inputs are available to monitor the temperature of the Ex p-protected equipment. Up to three switch values can be assigned to them.

The design of the SILASmv means that all components required for the pressurised enclosure are located in the control unit. The equipment to be monitored is connected to the Ex p control unit by means of a pipe, which allows a maximum purge volume of 70 litres.

The following components can also be connected:

- There is the option to connect a p operator panel

Technical Data

Protection class IP 66 according to EN/IEC 60529
IP 64 according to EN/IEC 60079-0
Pressure range 0 to 25 mbar for all pressure switching levels
Purge time 0 to 120 minutes (adjustable)
Temperatures Operating temperature
-25 °C to +60 °C @ T4 (-13 °F to 140 °F @ T4)
-25 °C to +50 °C @ T5 (-13 °F to 104 °F @ T5)
Storage temperature
-20 °C to +60 °C (-4 °F to 140 °F)
Voltage AC Variant:
AC 100 V up to 230 V
DC Variant:
DC 24 V up to 44 V
Material V4A stainless steel
Display 6 LEDs for status display
Relay Enable contact, switched input voltage max. load 5A
Enable relay, potentiel free, 4 NO
2x Signal relay for status transmission (potentail free), CO
Weight 9.8 kg

Manuals/Operating Instructions/Guides

  • Operating Instructions - SILASmv control unit

Declarations

Data Sheets

  • Data Sheet - SILASmv control unit