PROFIBUS-DP
Benefits
- Time flow refresh signal
- PROFIBUS coupler/PROFIBUS repeater also for hazardous areas of Zone 1
- Galvanically isolated bus segments for PROFIBUS-DP and PROFIBUS-IS
- Availability of couplers for PROFIBUS-DP as well as for PROFIBUS-IS (intrinsically safe)
Marking
Ex i:
Ex II 2(1)G Ex db e [ib] IIC Gb
Ex I M2 Ex db e [ib] I Mb
Ex db e [ib] IIC Gb
Ex db e [ib] I Mb
Class I Zone 1 IIC
A/Ex d e [ib] IIC Gb
Ex e:
Ex II 2(1)G Ex db e IIC Gb
Ex I M2 Ex db e I Mb
Ex db e IIC Gb
Ex db e I Mb
Class I Zone 1 IIC
A/Ex d e IIC Gb
Ambient Temperature
-25 °C to +60 °C at T4Description
The PROFIBUS devices have been particularly dimensioned for the industrial requirements of hazardous areas of zone 1. They are used for the separation or generation of new segments, converting the RS485 typical line structure into an open and flexible tree structure. Downstream stations can be coupled to and de-coupled from the superior bus system in a non-reactive and break/short-circuit tolerant manner, even during running bus operation.The devices facilitate a duplication of the signal to realize a redundant connection to a master. The devices are available as PROFIBUS-DP and as PROFIBUS-IS (intrinsically safe).
Technical Data
Protection class | Module: IP 66 EN/IEC 60529 Terminals: IP 20 EN/IEC 60529 Terminals with cover: IP 30 EN/IEC 60529 |
---|---|
Structure | Flameproof, clip-on enclosure for TH 35 rail |
Dimensions | (height x width x depth) 94 mm x 30 mm x 91 mm 94 mm x 75 mm x 91 mm |
Material | High-quality thermoplastic |
Storage temperature | -25 °C to +70 °C |
Weight | Module width 30 mm: 180 g Module width 75 mm: 250 g |
Display | LED green: Operational readiness LED green/yellow: Bus activity |
Voltage | Supply voltage: DC 20 V to 30 V |
Current | max. 70 mA |
Transmission rate | Ex e: Kbit/s- 4, 8/9, 6/19, 2/45, 45/93, 75/187, 5/250/375/500/750 Mbit/s- 1.0/1.5/2.0/3.0/6.0/12.0 Ex i: Kbit/s- 4, 8/9, 6/19, 2/45, 45/93, 75/187, 5/250/375/500/750 Mbit/s- 1.0/1.5 |