Product PLEXO TCS

PLEXO TCS

Plug-in connection technology for self-regulating heating cables
27-59P.-.01 / 27-1100-....

Benefits

  • Quick and easy installation, with standard tools
  • Integrated strain relief: high electrical and mechanical safety
  • System approval with PSB, MSB, HSB, and HSB+
Get a Quote

Marking

ATEX:

II 2G Ex eb 60079-30-1, IIC T3, T4, T5, T6 Gb
II 2D Ex tb 60079-30-1, IIIC T170 °C, T135 °C, T95 °C, T80 °C Db

IECEx:

Ex eb 60079-30-1, IIC T3, T4, T5, T6 Gb
Ex tb 60079-30-1, IIIC T170 °C, T135 °C, T95 °C, T80 °C Db

Ambient Temperature

-60 °C < Ta < +160 °C

Certification

  • ATEX Certificate
  • IECEx Certificate
  • UKEX Certificate

Description

The PLEXO TCS connection system can be used for BARTEC self-regulating heating cables. This modular connection technology enables the simple and reliable assembly of supply connections, splicing and remote-end terminations.
PLEXO TCS is plugged and built up with a patented sealing and clamping technology. Maintenance work and later modifications on the heating circuit can be performed quickly and flexibly. The strands from the heating cable or the supply cable are fixed in place securely using the spring-loaded terminals in the internal clamping technology.

Technical Data

Rated voltage max. 277 V
Max. breaker rating PSB / MSB / HSB / HSB+ : 32A, C-Characteristic
Protection class EN 60079-0: IP 65
EN 60529: IP 66/IP 68
Service temperature range -60 °C up to +160 °C
Rated cross-section max. 4 mm²
Min. installation temperature -55 °C
Cold cable diameter range 9 mm DA ≤ 10 mm
10 mm DA ≤ 12 mm
12 mm DA ≤ 14 mm
14 mm DA ≤ 16 mm