	PAPD cable glands
Ex d double seal cable glands for zone 1/2 - 21/22
				PAPD..PAPDB
				
	
		Benefits
- For steel wire armoured cables (SWA) for steel tape armoured cables and for lead inner sheath cables
- Double Compression type for Indoor and Outdoor use
- IP 66 or IP66/68
- Barrier cable glands series PAPDB
Marking
ATEX:
 (Ex II 2 G) Ex db IIC Gb
 (Ex II 2 G) Ex eb IIC Gb
 (Ex II 2 G) Ex ia IIC Gb
 (Ex II 2 D) Ex tb IIIC Db
 (EX II 3 G) Ex nR IIC Gc
 (EX II 3 D) Ex tc IIIC Dc IP66 or IP68
 
 IECEx:
 Ex db IIC Gb
 Ex eb IIC Gb
 Ex ia IIC Gb
 Ex nR IIC Gc
 Ex tb IIIC Db
 Ex tc IIIC Dc
 IP66 or IP66/68
Ambient Temperature
-40 °C to +90 °C standard(rubber rings EPDM-60)
-60 °C to +180 °C on demand
(rubber rings SILICON)
Product Video
Description
Flameproof Ex d cable glands for armoured and lead sheathed cables BARTEC PAPD series are designed to be installed in industrial plants, where potential hazardous atmospheres occur.
 These areas are either classified as zone 1 and 2 or as zone 21 and 22.
 Suitable for:
- steel wire armoured cables (SWA),
- steel tape armoured cables
- lead inner sheath cables
This cable gland PAPD.. - PAPD-B.. series has double compression type for indoor and outdoor use
Technical Data
| Protection class | IP 66 or IP 68 (IEC/EN 60529) | 
|---|---|
| Material | Marine grade Aluminium alloy Stainless steel AISI 316L Nickel plated brass OT-58 | 
| Weight | see data sheet | 
| Dimensions | see data sheet | 
| Accessories | |
| Quantity of cable entries | |
| Voltage | |
| Current | |
| Imapct test | 
 
			 
			 
			 
			 
			 
			 
			 
			 
			 
			