Dust Proof Electrical Motors
Benefits
Highest degree of safety and reliability
Certified for dust group IIIC (conductive dusts, non-conductive dust and combustible flyings)
Modular design, which allows execution of all IEC forms and different positions/rotations of connection box
Many international and local approvals (ATEX, IECEx, Kosha and many more)
Ingress protection range: IP65
Suitable for Ambient Temperatures from -50°C to +85°C
Temperature class T135°C as a standard, other variants also available on request
Marking
ATEX:
II 2D Ex tb IIIC T135°C Db
IECEx:
Ex tb IIIC T135°C Db
Ingress protection
Standard IP65
Ambient temperature
Standard -20 °C up to +40 °C
On request from -30 °C up to +85 °C
Ambient Temperature
Standard: -20 °C up to +40 °COn request: -50 °C up to +85 °C
Description
Dust-proof electric motors are used in industrial plants with a potentially explosive dust atmosphere, containing conductive dust, non-conductive dust and combustible flyings). The enclosures of electric motors are designed to be "flameproof" according to EN 60079-0 (IEC 60079-1).
Technical Data
These are three-phase asynchronous electric motors with shot-circuit rotor, according to the EN 60079-0, EN 600079-1, EN 600079-7 and EN 60079-31 standards.
- Efficiency class IE1, IE2, IE3
- Efficiency class IE4 on request
- Enclosure Ex tb (cast iron flameproof design)
- Frame size 71 - 315
- Power up to 200 kW
Manuals/Operating Instructions/Guides
-
Manual instructions / 4KTC 71-132
-
Manual instructions / 4KTC 160-225
-
Manual instructions / 4KTC 250-315
-
Manual instructions / 5KTC 250-315