| Nominal voltage | AC 208 V to 277 V AC 110 V to 120 V |
|---|---|
| Max. continuous operating temperature, energized | +150 °C |
| Max. continuous exposure temperature, de-energized | +225 °C |
| Min. installation temperature | -40 °C |
| Min. start-up temperature | -40 °C |
| Temperature class | T3 |
| Max. braid resistance | 18.2 Ohm/km |
| Dimensions with braiding and jacket | 11.4 x 5.2 mm |
| Min. bending radius | 35 mm |
ATEX:
II 2G Ex 60079-30-1 IIC T3 Gb
II 2D Ex 60079-30-1 IIIC T200°C Db
IECEx:
Ex 60079-30-1 IIC T3 Gb
Ex 60079-30-1 IIIC T200°C
Max. continuous operating temperature, energized
+150 °C
Max. continuous exposure temperature, de-energized
+225 °C
Minimum installation temperature
-40 °C
Minimum start-up temperature
-40 °C
The self-regulating heating cable HSB+ is suitable for frost protection and temperature maintenance on pipes and vessels at high process temperatures in industry and hazardous areas. It can be used where steam cleaning is required.
The power output of the HSB+ varies depending on the ambient temperature. If the ambient temperature increases, the heating output will be reduced.
With the fluoropolymer protective jacket, the heating cable is resistant to most chemicals.