PBS/PBM-310 for BPL-AL

Power entry for BPL-AL
27-54P3-...
Benefits
  • Mounting bracket and plate included
  • Including cold applied power and end termination kit (CAK)
  • Fast installation and maintenance-free operation with spring type terminals
  • System certified
Get a Quote
Rated Voltage 277V
Protection class ATEX & IECEx types: IP 64
North America: Type 4X
Max. breaker rating ATEX & IECEx types: 32A, C-Characteristic
North America: 40A
Terminals Ex e, Spring Type, 6 mm² / 14 AWG
optionally 10 mm² / 12 AWG
Materials Enclosure: Polyester, glass fibre reinforced
Mounting bracket and plate: galvanized Steel

PBS/PBM-310-E*:
ATEX:
II 2G Ex eb 60079-30-1 IIC T6…110°C(T4) Gb
II 2D Ex tb 60079-30-1 IIIC TL80…TL110°C Db
IECEx:
Ex eb 60079-30-1 IIC T6…110°C(T4) Gb
Ex tb 60079-30-1 IIIC TL80…TL110°C Db

BPL-AL System:
ATEX:
II 2G Ex eb 60079-30-1 IIC T6…T1 Gb
II 2D Ex tb 60079-30-1 IIIC TL80…TL450°C Db
IECEx:
Ex eb 60079-30-1 IIC T6…T1 Gb
Ex tb 60079-30-1 IIIC TL80…TL450°C Db

PBS/PBM-310-*:
Min. installation temperature
-55 °C
-67 °F
Ambient temperature
-55 °C to +55 °C
-67 °F to +131 °F

CAK-PLH-*:
Min. installation temperature
-40 °C
-40 °F
Max. operating temperature
+200 °C
+392 °F

Description

The PBS Single Entry Power junction box is designed to connect one BARTEC parallel constant wattage heating cable BPL-AL to power.
The PBM Multiple Entry Power junction box is designed to connect up to three BARTEC parallel constant wattage heating cable BPL-AL to power or splice up to three trace heaters.
Sufficient CAK connection and termination kits are included with every PBS and PBM but can also be ordered separately.
The mounting bracket and plate are also included for every PBS and PBM.

The -E variant is available with cable glands on the side as power entries, while the -A variant is available for conduit connections.

PBS/PBM-310 are part of the BPL-AL-System and can therefore be used safely in hazardous and industrial zones.