Isolator relay

contact seperation as per DIN EN 60079-0, DIN EN 60079-11 for zone 1/21
07-7311-937./..00
Benefits
  • Safe galvanic isolation
Get a Quote
Protection class Module: IP 66/IEC 60529
Terminals: IP 20/IEC 60529
Material High-quality thermoplastic
Contact material AgCuNi
Installation TH 35 x 7.5 (15) EN 60715
Storage temperature -40 °C to +70 °C
Weight 0.250 kg
Voltage see data sheet
Current see data sheet
Connection Terminals 2.5 mm², fine stranded

Ex II 2(1)G Ex de [ia Ga] IIC Ga
Ex db e IIC / Ex d e [ia Ga] IIC Ga
Ex db e I / Ex d e [ia Ma] I Mb
Class I, Zone 1, IIC
A/Ex d e [ia] IIC Ga

25 °C to +55 °C (DC 12 V/24 V)
at T6 and 15 mm distance

Description

This relay is used as an isolator between non-intrinsically safe and intrinsically safe circuits. Various coil and contact configurations are available. Several intrinsically safe circuits can be connected to the contact circuits, provided that intrinsic safety is maintained. Safe galvanic isolation in conformance to EN/IEC 60079-11 up to 375 V is provided between the coil and contacts.