Product EXL LED or fluorescent emergency light

EXL LED or fluorescent emergency light

Ex d Flameproof lighting fixture for zone 1/21
EXL…

Benefits

  • High efficiency
  • Long lifetime
  • Zone 1, 2, 21, 22
Get a Quote

Marking

LED

ATEX:
Ex II 2G Ex dp op is IIB+H2 T6... T5 Gb
Ex II 2D Ex op is tb IIIC T85°C ... T100°C Db IP66
IECEx:
Ex db op is IIB+H2 T6 ... T5 Gb
Ex op is tb IIIC T85°C ... T100°C Db IP66

Fluorescent

ATEX:
Ex II 2G Ex db IIB+H2 T6 ... T5 Gb
Ex II 2D Ex tb IIIC T85°C ... T100°C Db IP66
IECEx:
Ex d IIB+H2 T6 ... T5 Gb
Ex tb IIIC T85°C ... T100°C Db IP66

 

Ambient Temperature

-60°C to +80°C
-60°C to +60°C

Certification

Description

The Type EXL linear luminaire with fluorescent lamp or LED tube is an explosion protected item of operating equipment with lamp sockets for fluorescent lamps Type T5 (Ø16) with G5 base or LED strips up to a max. 9.6W. It is ideally suited as an emergency light for safety lighting or as an illuminated sign at operating and storage facilities in potentially explosive areas, and may be deployed in Zones 1, 2 as well as 21 and 22.

The luminaire, designed with type of protection “Ex d”, is available with various operating modes. In addition to the mains dependent operation (NETWORK ONLY), the luminaire may also be fitted with emergency light electronics. This enables permanent operation (ALWAYS ON) as well as functional operation only for up to three hours in the event of a power failure (EMERGENCY ONLY). An “Ex d” cable gland ¾” NPT is available for the electrical connection. The Type EXL luminaire is suitable for wall or ceiling mounting.

Technical Data

Protection degree IP66 (IEC/ EN 60529)
Dimensions see data sheet
Material 1.4404, AISI 316 L high quality stainless steel
optional: 1.4301, AISI 304 high quality stainless steel
Surface: brushed, painted or electro polished on request
Weight see data sheet
Voltage

Power supply (fluo)
230V/240V 50/60Hz (cos ρ ≥ 0,98)

Power supply (led)
110V/240V 50/60Hz
230V/240V 50/60Hz

Questionnaires/Requirement Sheets

  • Customer requirements - Lighting

Manuals/Operating Instructions/Guides

Declarations

  • EU Declaration of conformity

Data Sheets