EKL Premium Serial Resistance Heating Cable

Series resistance polymer insulated heating cables
27-582.-756K….
Benefits
  • Constant power output per meter
  • Resistant to steam purging
  • High resistance to chemicals
  • Simple installation, simple assembly on site
  • Suitable for applications in explosive area (7J impact resistance)
Get a Quote

 

Nominal voltage 450V/750V
Min. bending radius 25 mm for types 1R08 and 1R71
15 mm for all other types
Protective braid resistance 18.0 Ohm/km
Shock resistance 7 Joule

EKL Heating Cable:
ATEX:
II 2G Ex 60079-30-1 IIC Gb
II 2D Ex 60079-30-1 IIIC Db
IECEx:
Ex 60079-30-1 IIC Gb
Ex 60079-30-1 IIIC Db

EKL System:
ATEX:
II 2G Ex 60079-30-1 IIC T3, T4, T5, T6 Gb
II 2D Ex 60079-30-1 IIIC T195°C, T130°C, T95°C, T80°C Db
IECEx:
Ex 60079-30-1 IIC T3, T4, T5, T6 Gb
Ex 60079-30-1 IIIC T195°C, T130°C, T95°C, T80°C Db

Operating temperature:
-60 °C to +260 °C

Description

EKL premium is a serial resistance heating cable for use in hazardous and industrial areas. It is suitable for frost protection applications and temperature maintenance on pipes and tanks and is also extremely flexible.
This makes EKL premium easy to install, even on irregular shapes such as on pumps, valves and flanges. The PFA protective jacket gives the EKL premium a high degree of chemical and mechanical resistance, even at high temperatures.

EKL premium is available as a part of the EKL system.
The EKL system consists of EKL cold leads, EKL heating cable and the EKL connection technology ECT.
With the EKL system, it is possible to design and install a heating circuit either with controlled or stabilized design in accordance with the BARTEC design guide for the EKL system without further testing required by a notified body. A qualified person can inspect and release the final installation.