| Nominal voltage | 450V/750V |
|---|---|
| Operating Temperature | -60 °C to +260 °C |
| Min. installation temperature | -60 °C |
| Min. bending radius | 25 mm for types 1R08 and 1R71 15 mm for all other types |
| Protective braid resistance | 18.0 Ohm/km |
| Shock resistance | 7 Joule |
ATEX:
II 2G Ex 60079-30-1 IIC Gb
II 2D Ex 60079-30-1 IIIC Db
IECEx:
Ex 60079-30-1 IIC Gb
Ex 60079-30-1 IIIC Db
Operating temperature:
-60 °C to +260 °C
EKL premium is a serial resistance heating cable for use in hazardous and industrial areas. It is suitable for frost protection applications and temperature maintenance on pipes and tanks and is also extremely flexible.
This makes EKL premium easy to install, even on irregular shapes such as on pumps, valves and flanges. The PFA protective jacket gives the EKL premium a high degree of chemical and mechanical resistance, even at high temperatures.