| Protection class | IP 65 |
|---|---|
| Dimensions | see data sheet Max. Ex px control cabinet capacity: 2,000 litres |
| Pressure | 0 to 16 bar |
| Weight | approx. 1.2 kg |
| Voltage | AC 230 V/9 W/50 to 60 Hz AC 115 V/9 W/50 to 60 Hz DC 24 V/9 W Voltage tolerance: ± 10% |
| Connection | Valve connection: G 3/8“ Nominal diameter: 13 mm |
ATEX:
Ex II 2G Ex mb IIC T4 Gb
Ex II 2D Ex mb IIIC T130°C Db
IECEx:
Ex mb IIC T4 Gb
Ex mb IIIC T130°C Db
Operating temperature
-40 °C to +55 °C @ T4
(-40 °F to 131 °F @ T4)
Storage temperature
-20 °C to +60 °C
(-4 °F to 140 °F)
The digital purge gas valve controlled by the APEX or SILAS control unit directs the supplied purging gas into the Ex p control cabinet.
During the purge phase, the purge gas valve opens and thus ensures a purging pressure in the encapsulated control cabinet.
After the purge phase, the purge gas valve closes.
Any leakage losses occurring in the Ex p control cabinet are compensated for by an integrated adjustable leakage air needle valve.